Global warming potentials (GWP-100) for the refrigerants found in Australian HVAC, cold chain, vehicle and industrial equipment. NGER uses the AR5 set fixed in regulation 2.02 of the NGER Regulations (HFCs and SF6 only; R-22 is an HCFC and not an NGER gas). AASB S2 references AR6. Blends are mass-weighted from their components. Multiply kilograms of refrigerant lost by the GWP to get kg CO2-e.
| Refrigerant | Chemistry | AR5 GWP (NGER) | AR6 GWP (AASB S2) | Common use |
|---|---|---|---|---|
| R-22 | CHClF2 (HCFC) | 1760 | 1960 | Older residential and commercial AC, being phased out. An HCFC, not listed for NGER |
| R-32 | CH2F2 (HFC) | 677 | 771 | Modern residential AC, replacing R-410A in new equipment |
| R-134a | CH2FCF3 (HFC) | 1300 | 1530 | Automotive AC, medical inhalers, commercial refrigeration |
| R-404A | HFC blend (44/4/52) | 3943 | 4728 | Supermarket display cases, cold storage, transport refrigeration |
| R-407C | HFC blend (23/25/52) | 1624 | 1908 | AC and heat pumps, R-22 replacement in split systems |
| R-410A | HFC blend (50/50 R-32/R-125) | 1924 | 2256 | Split system AC, most common residential and light commercial |
| R-448A | HFC/HFO blend | 1273 | 1494 | Lower-GWP replacement for R-404A in commercial refrigeration |
| R-449A | HFC/HFO blend | 1282 | 1504 | R-404A replacement in supermarket and cold storage |
| R-507A | HFC blend (50/50 R-125/R-143a) | 3985 | 4775 | Low-temperature commercial refrigeration |
| R-1234yf | HFO CH2=CFCF3 | <1 | <1 | New-vehicle AC (post-2017), low-GWP HFO |
| R-1234ze | HFO CHF=CHCF3 | <1 | 1 | Chillers and vending, low-GWP HFO |
| R-290 | Propane C3H8 | 3 | 0 | Small commercial refrigeration, natural refrigerant |
| R-600a | Isobutane C4H10 | 3 | 0 | Domestic refrigerators and freezers |
| R-717 | Ammonia NH3 | 0 | 0 | Industrial refrigeration, cold stores, food processing |
| R-744 | Carbon dioxide CO2 | 1 | 1 | Trans-critical supermarket systems, heat pumps |
Figures such as 2,088 for R-410A are AR4 values and are not NGER values. Related: refrigerant emissions and Scope 1 fugitive reporting, AR5 versus AR6 GWPs, refrigerant leak calculator, refrigerants hub.
R-410A has a Global Warming Potential of 1,924 under AR5 (the set NGER uses) and 2,256 under AR6 (used by AASB S2). A 10 kg leak from a split system is 19 to 23 tonnes of CO2-equivalent depending on which reporting regime applies. The 2,088 figure often quoted for R-410A is the older AR4 value.
AR5 for NGER submissions, using the values set in regulation 2.02 of the NGER Regulations. AR6 for AASB S2 climate-related disclosures aligned to ISSB IFRS S2. AASB S2025-1 lets the NGER-covered portion of an AASB S2 disclosure keep the AR5 numbers; check which set the rest of your disclosure needs.
R-11, R-12 and R-22 are already restricted under the Montreal Protocol as ozone-depleting substances. Under the Kigali Amendment Australia is progressively restricting high-GWP HFCs including R-404A, R-410A and R-507A. New equipment increasingly uses low-GWP alternatives like R-32, R-290, R-1234yf and CO2.
Multiply the kilograms of refrigerant lost during the year (from top-ups and service records) by the GWP of that specific refrigerant. A 5 kg leak of R-134a is 5 x 1,530 = 7,650 kg CO2-e = 7.65 tonnes under AR6. Applies to service refills, end-of-life disposal losses, and any leak captured by your maintenance log.