Refrigerant GWP table for Australian reporters

Global warming potentials (GWP-100) for the refrigerants found in Australian HVAC, cold chain, vehicle and industrial equipment. NGER uses the AR5 set fixed in regulation 2.02 of the NGER Regulations (HFCs and SF6 only; R-22 is an HCFC and not an NGER gas). AASB S2 references AR6. Blends are mass-weighted from their components. Multiply kilograms of refrigerant lost by the GWP to get kg CO2-e.

GWP by refrigerant

RefrigerantChemistryAR5 GWP (NGER)AR6 GWP (AASB S2)Common use
R-22CHClF2 (HCFC)17601960Older residential and commercial AC, being phased out. An HCFC, not listed for NGER
R-32CH2F2 (HFC)677771Modern residential AC, replacing R-410A in new equipment
R-134aCH2FCF3 (HFC)13001530Automotive AC, medical inhalers, commercial refrigeration
R-404AHFC blend (44/4/52)39434728Supermarket display cases, cold storage, transport refrigeration
R-407CHFC blend (23/25/52)16241908AC and heat pumps, R-22 replacement in split systems
R-410AHFC blend (50/50 R-32/R-125)19242256Split system AC, most common residential and light commercial
R-448AHFC/HFO blend12731494Lower-GWP replacement for R-404A in commercial refrigeration
R-449AHFC/HFO blend12821504R-404A replacement in supermarket and cold storage
R-507AHFC blend (50/50 R-125/R-143a)39854775Low-temperature commercial refrigeration
R-1234yfHFO CH2=CFCF3<1<1New-vehicle AC (post-2017), low-GWP HFO
R-1234zeHFO CHF=CHCF3<11Chillers and vending, low-GWP HFO
R-290Propane C3H830Small commercial refrigeration, natural refrigerant
R-600aIsobutane C4H1030Domestic refrigerators and freezers
R-717Ammonia NH300Industrial refrigeration, cold stores, food processing
R-744Carbon dioxide CO211Trans-critical supermarket systems, heat pumps

Figures such as 2,088 for R-410A are AR4 values and are not NGER values. Related: refrigerant emissions and Scope 1 fugitive reporting, AR5 versus AR6 GWPs, refrigerant leak calculator, refrigerants hub.

Frequently asked questions

What is the GWP of R-410A?

R-410A has a Global Warming Potential of 1,924 under AR5 (the set NGER uses) and 2,256 under AR6 (used by AASB S2). A 10 kg leak from a split system is 19 to 23 tonnes of CO2-equivalent depending on which reporting regime applies. The 2,088 figure often quoted for R-410A is the older AR4 value.

Do I report refrigerants under AR5 or AR6?

AR5 for NGER submissions, using the values set in regulation 2.02 of the NGER Regulations. AR6 for AASB S2 climate-related disclosures aligned to ISSB IFRS S2. AASB S2025-1 lets the NGER-covered portion of an AASB S2 disclosure keep the AR5 numbers; check which set the rest of your disclosure needs.

Which refrigerants are being phased out in Australia?

R-11, R-12 and R-22 are already restricted under the Montreal Protocol as ozone-depleting substances. Under the Kigali Amendment Australia is progressively restricting high-GWP HFCs including R-404A, R-410A and R-507A. New equipment increasingly uses low-GWP alternatives like R-32, R-290, R-1234yf and CO2.

How do I calculate refrigerant emissions?

Multiply the kilograms of refrigerant lost during the year (from top-ups and service records) by the GWP of that specific refrigerant. A 5 kg leak of R-134a is 5 x 1,530 = 7,650 kg CO2-e = 7.65 tonnes under AR6. Applies to service refills, end-of-life disposal losses, and any leak captured by your maintenance log.